Jefferson County, ALCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Golden Animal Hospital

Approved

Filed Apr 12, 2026 by Drew Harlow, Summit Plumbing & Backflow · filed from phone

Report

Date of service
Apr 12, 2026
Assembly type
RP
Serial number
B728330
Size
4
Test gauge serial
G-1499
Gauge calibration date
May 25, 2025
Check valve 1
3.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Relief valve opened at
1.2 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 073-66-01297
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

4157 Laurel Trl
Owner: Nguyen Holdings LLC
Parcel 073-66-01297