Backflow assembly test · 8006 Cedar Hollow Trl

Approved

Filed Aug 28, 2025 by Morgan Marsh, Summit Plumbing & Backflow · filed from phone

Report

Date of service
Aug 28, 2025
Assembly type
RP
Serial number
W814661
Size
1
Test gauge serial
G-5661
Gauge calibration date
Apr 28, 2024
Check valve 1
0.1 psid
Check valve 1 closed tight
No
Check valve 2
2.8 psid
Relief valve opened at
2.5 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 073-47-01177
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.