← Backflow review queue
Backflow assembly test · 6229 Quarry Trl
ApprovedFiled Oct 4, 2023 by Morgan Marsh, Summit Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Oct 4, 2023
- Assembly type
- RP
- Serial number
- K900567
- Size
- 1
- Test gauge serial
- G-7211
- Gauge calibration date
- Dec 15, 2022
- Check valve 1
- 6.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Relief valve opened at
- 2.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 073-56-01015
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
6229 Quarry Trl
Owner: Casey Stroud
Parcel 073-56-01015