← Backflow review queue
Backflow assembly test · 3002 Turkey Hill Rd
ApprovedFiled Nov 13, 2026 by Drew Harlow, Summit Plumbing & Backflow · filed from phone
Report
- Date of service
- Nov 13, 2026
- Assembly type
- RP
- Serial number
- Z198584
- Size
- 3/4
- Test gauge serial
- G-2099
- Gauge calibration date
- Jun 7, 2026
- Check valve 1
- 4.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.7 psid
- Relief valve opened at
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 073-39-01025
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
3002 Turkey Hill Rd
Owner: Casey Okafor
Parcel 073-39-01025