Backflow assembly test · Two Rivers Elementary School
ApprovedFiled Aug 2, 2025 by Casey Whitcomb, Northstar Plumbing & Backflow · filed from phone
Report
- Date of service
- Aug 2, 2025
- Assembly type
- DC
- Serial number
- A629315
- Size
- 1 1/2
- Test gauge serial
- G-8255
- Gauge calibration date
- Jun 24, 2024
- Check valve 1
- 0.6 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.6 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 073-24-01359
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.