Coconino County, AZCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 2527 Old Church Way

Approved

Filed Oct 27, 2025 by Drew Stroud, Keystone Backflow Testing · filed from phone

Report

Date of service
Oct 27, 2025
Assembly type
RP
Serial number
W164194
Size
1
Test gauge serial
G-4963
Gauge calibration date
Jun 30, 2025
Check valve 1
6.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
2.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 005-58-01333
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

2527 Old Church Way
Owner: Drew Ramirez
Parcel 005-58-01333