Backflow assembly test: Blue Heron Diner

Approved

Filed May 14, 2025 by Cameron Okafor, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
May 14, 2025
Assembly type
RP
Serial number
A741687
Size
1 1/2
Test gauge serial
G-6734
Gauge calibration date
Oct 23, 2024
Check valve 1
3.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Okafor, current on the service date
  • All required fields present
  • Address matches parcel 005-80-01214
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9217 Mill Creek Ln
Owner: Nguyen Holdings LLC
Parcel 005-80-01214