Coconino County, AZCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 460 Orchard Rd

Approved

Filed Sep 16, 2025 by Hayden Stroud, Keystone Backflow Testing · filed from phone

Report

Date of service
Sep 16, 2025
Assembly type
RP
Serial number
A656179
Size
3/4
Test gauge serial
G-7403
Gauge calibration date
Feb 25, 2025
Check valve 1
8.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 005-92-01184
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

460 Orchard Rd
Owner: Cameron Vance
Parcel 005-92-01184