← Backflow review queue
Backflow assembly test · Station Pizza
ApprovedFiled Dec 10, 2025 by Taylor Benton, Ridge Plumbing & Backflow · filed from phone
Report
- Date of service
- Dec 10, 2025
- Assembly type
- RP
- Serial number
- W788307
- Size
- 1
- Test gauge serial
- G-4321
- Gauge calibration date
- Apr 13, 2025
- Check valve 1
- 6.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.7 psid
- Relief valve opened at
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 005-17-01327
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
3015 Old Church Rd
Owner: Ellery Holdings LLC
Parcel 005-17-01327