Coconino County, AZCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 3021 Mill Creek Ct

Approved

Filed Jan 2, 2024 by Hayden Stroud, Keystone Backflow Testing · filed from phone

Report

Date of service
Jan 2, 2024
Assembly type
RP
Serial number
Z892740
Size
1
Test gauge serial
G-8421
Gauge calibration date
Jul 12, 2023
Check valve 1
5.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 005-50-01320
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3021 Mill Creek Ct
Owner: Morgan Fairley
Parcel 005-50-01320