Coconino County, AZCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 711 Cedar Hollow Way

Approved

Filed Feb 10, 2026 by Taylor Benton, Ridge Plumbing & Backflow · filed from phone

Report

Date of service
Feb 10, 2026
Assembly type
RP
Serial number
A923734
Size
1
Test gauge serial
G-9819
Gauge calibration date
May 20, 2025
Check valve 1
0.6 psid
Check valve 1 closed tight
No
Check valve 2
1.1 psid
Relief valve opened at
3.2 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 005-54-01016
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

711 Cedar Hollow Way
Owner: Morgan Okafor
Parcel 005-54-01016