Backflow assembly test · Maple Leaf Dental

Approved

Filed Jan 2, 2026 by Jamie Harlow, Summit Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Jan 2, 2026
Assembly type
DC
Serial number
Z538795
Size
2
Test gauge serial
G-4187
Gauge calibration date
Apr 28, 2025
Check valve 1
0.6 psid
Check valve 1 closed tight
No
Check valve 2
2.4 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 013-41-01277
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8755 Fox Run Rd
Owner: Fairley Holdings LLC
Parcel 013-41-01277