Maricopa County, AZCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 8798 Cedar Hollow Way

Approved

Filed Nov 17, 2025 by Jamie Harlow, Summit Plumbing & Backflow · filed from phone

Report

Date of service
Nov 17, 2025
Assembly type
RP
Serial number
A665287
Size
1
Test gauge serial
G-3529
Gauge calibration date
Feb 7, 2025
Check valve 1
6.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 013-84-01138
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8798 Cedar Hollow Way
Owner: Avery Stroud
Parcel 013-84-01138