Maricopa County, AZCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 8241 Orchard Trl

Approved

Filed Nov 6, 2025 by Hayden Danner, Northstar Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Nov 6, 2025
Assembly type
RP
Serial number
B224741
Size
1
Test gauge serial
G-8494
Gauge calibration date
Jun 26, 2025
Check valve 1
4.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 013-81-01173
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8241 Orchard Trl
Owner: Cameron Ramirez
Parcel 013-81-01173