Pima County, AZCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Crossroads Pizza

Approved

Filed Dec 7, 2025 by Sam Brandt, Patriot Backflow Testing · filed from phone

Report

Date of service
Dec 7, 2025
Assembly type
RP
Serial number
W705458
Size
1 1/2
Test gauge serial
G-4323
Gauge calibration date
Sep 16, 2025
Check valve 1
8.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Relief valve opened at
1.7 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 019-46-01342
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6888 Hickory Dr
Owner: Pruitt Holdings LLC
Parcel 019-46-01342