Pima County, AZCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Station Apartments

Approved

Filed Oct 27, 2026 by Logan Vance, Lakeside Backflow Testing · filed from phone

Report

Date of service
Oct 27, 2026
Assembly type
DC
Serial number
K771601
Size
4
Test gauge serial
G-6568
Gauge calibration date
Aug 8, 2026
Check valve 1
8.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 019-95-01008
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1965 Ridgeview Trl
Owner: Benton Holdings LLC
Parcel 019-95-01008