← Backflow review queue
Backflow assembly test · Riverside Self Storage
ApprovedFiled Nov 17, 2025 by Hayden Stroud, Patriot Backflow Testing · filed from phone
Report
- Date of service
- Nov 17, 2025
- Assembly type
- RP
- Serial number
- W902764
- Size
- 2
- Test gauge serial
- G-6487
- Gauge calibration date
- Aug 11, 2025
- Check valve 1
- 6.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.8 psid
- Relief valve opened at
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 019-14-01162
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
8018 Laurel Dr
Owner: Stroud Holdings LLC
Parcel 019-14-01162