← Backflow review queue
Backflow assembly test · 6335 Meadow Lark Dr
ApprovedFiled Aug 12, 2024 by Riley Kessler, Patriot Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Aug 12, 2024
- Assembly type
- RP
- Serial number
- A285798
- Size
- 1
- Test gauge serial
- G-4362
- Gauge calibration date
- May 30, 2024
- Check valve 1
- 7.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.6 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 019-42-01065
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
6335 Meadow Lark Dr
Owner: Jamie Stroud
Parcel 019-42-01065