Backflow assembly test · Station Bakery
ApprovedFiled Jul 10, 2025 by Avery Ramirez, Clearwater Backflow Testing · filed from phone
Report
- Date of service
- Jul 10, 2025
- Assembly type
- RP
- Serial number
- A312326
- Size
- 2
- Test gauge serial
- G-2499
- Gauge calibration date
- Aug 1, 2024
- Check valve 1
- 0.4 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 4 psid
- Relief valve opened at
- 2.9 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 021-83-01224
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
4004 Hickory Ct
Owner: Lindqvist Holdings LLC
Parcel 021-83-01224