Backflow assembly test · 5221 Cedar Hollow Dr
ApprovedFiled Dec 23, 2025 by Avery Ramirez, Clearwater Backflow Testing · filed from phone
Report
- Date of service
- Dec 23, 2025
- Assembly type
- RP
- Serial number
- A133008
- Size
- 3/4
- Test gauge serial
- G-4013
- Gauge calibration date
- Apr 25, 2025
- Check valve 1
- 6.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 4 psid
- Relief valve opened at
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 021-90-01163
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.