← Backflow review queue
Backflow assembly test · 6415 Quarry Rd
ApprovedFiled Nov 6, 2026 by Riley Pruitt, Heritage Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Nov 6, 2026
- Assembly type
- DC
- Serial number
- Z480151
- Size
- 3/4
- Test gauge serial
- G-5333
- Gauge calibration date
- Aug 24, 2026
- Check valve 1
- 0.9 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.9 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 021-64-01332
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
6415 Quarry Rd
Owner: Taylor Ellery
Parcel 021-64-01332