Pinal County, AZCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 4092 Mill Creek Rd

Approved

Filed Nov 10, 2026 by Drew Stroud, Clearwater Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Nov 10, 2026
Assembly type
RP
Serial number
B220327
Size
3/4
Test gauge serial
G-6449
Gauge calibration date
May 17, 2026
Check valve 1
3.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
4.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 021-24-01035
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4092 Mill Creek Rd
Owner: Drew Marsh
Parcel 021-24-01035