Pinal County, AZCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 5598 Orchard Way

Approved

Filed Jun 21, 2026 by Morgan Stroud, Patriot Plumbing & Backflow · filed from phone

Report

Date of service
Jun 21, 2026
Assembly type
RP
Serial number
K334286
Size
3/4
Test gauge serial
G-9651
Gauge calibration date
Nov 22, 2025
Check valve 1
7.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Relief valve opened at
4.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 021-99-01168
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

5598 Orchard Way
Owner: Emerson Brandt
Parcel 021-99-01168