Backflow assembly test · 7446 Ridgeview Way
ApprovedFiled Jun 21, 2024 by Reese Calloway, Northstar Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Jun 21, 2024
- Assembly type
- RP
- Serial number
- B831413
- Size
- 1
- Test gauge serial
- G-7954
- Gauge calibration date
- Mar 2, 2024
- Check valve 1
- 3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.4 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 025-28-01183
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.