Backflow assembly test · Crossroads Brewing Co
ApprovedFiled Jan 15, 2026 by Sam Nguyen, Clearwater Backflow Testing · filed from phone
Report
- Date of service
- Jan 15, 2026
- Assembly type
- RP
- Serial number
- W980036
- Size
- 1 1/2
- Test gauge serial
- G-1483
- Gauge calibration date
- Dec 16, 2025
- Check valve 1
- 4.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.1 psid
- Relief valve opened at
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 025-72-01172
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.