← Backflow review queue
Backflow assembly test · 438 Ridgeview Ln
ApprovedFiled Aug 27, 2023 by Reese Calloway, Northstar Plumbing & Backflow · filed from phone
Report
- Date of service
- Aug 27, 2023
- Assembly type
- RP
- Serial number
- A568818
- Size
- 3/4
- Test gauge serial
- G-1184
- Gauge calibration date
- Dec 21, 2022
- Check valve 1
- 0.8 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.3 psid
- Relief valve opened at
- 3.9 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 025-68-01182
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.