Backflow assembly test · 8485 Turkey Hill Dr
ApprovedFiled Aug 31, 2025 by Cameron Danner, Northstar Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Aug 31, 2025
- Assembly type
- DC
- Serial number
- K719360
- Size
- 3/4
- Test gauge serial
- G-4177
- Gauge calibration date
- Apr 3, 2025
- Check valve 1
- 4.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 025-90-01175
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.