← Backflow review queue
Backflow assembly test · Main Street Apartments
ApprovedFiled Dec 13, 2025 by Avery Harlow, Valley Backflow Testing · filed from phone
Report
- Date of service
- Dec 13, 2025
- Assembly type
- RP
- Serial number
- A197960
- Size
- 1
- Test gauge serial
- G-5602
- Gauge calibration date
- Aug 15, 2025
- Check valve 1
- 0.5 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.2 psid
- Relief valve opened at
- 2.5 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 025-81-01353
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
1034 Orchard Way
Owner: Vance Holdings LLC
Parcel 025-81-01353