Yavapai County, AZCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Hilltop Animal Hospital

Approved

Filed Aug 17, 2026 by Sam Nguyen, Clearwater Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Aug 17, 2026
Assembly type
RP
Serial number
K108487
Size
4
Test gauge serial
G-8360
Gauge calibration date
Jan 29, 2026
Check valve 1
8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 025-46-01305
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

7067 Turkey Hill Ln
Owner: Ramirez Holdings LLC
Parcel 025-46-01305