Backflow assembly test · 5847 Old Church Ct
ApprovedFiled Oct 9, 2024 by Logan Whitcomb, Evergreen Plumbing & Backflow · filed from phone
Report
- Date of service
- Oct 9, 2024
- Assembly type
- RP
- Serial number
- Z386573
- Size
- 1
- Test gauge serial
- G-6365
- Gauge calibration date
- Sep 2, 2024
- Check valve 1
- 5.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Relief valve opened at
- 1.2 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 027-78-01207
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.