← Backflow review queue
Backflow assembly test · 3793 Orchard Way
ApprovedFiled Jul 30, 2026 by Logan Whitcomb, Evergreen Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Jul 30, 2026
- Assembly type
- DC
- Serial number
- B769487
- Size
- 3/4
- Test gauge serial
- G-4795
- Gauge calibration date
- Dec 26, 2025
- Check valve 1
- 8.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 027-47-01082
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
3793 Orchard Way
Owner: Avery Okafor
Parcel 027-47-01082