Backflow assembly test · Golden Apartments

Approved

Filed Aug 24, 2026 by Jordan Pruitt, Keystone Backflow Testing · filed from phone

Report

Date of service
Aug 24, 2026
Assembly type
RP
Serial number
B104696
Size
4
Test gauge serial
G-9882
Gauge calibration date
Jan 19, 2026
Check valve 1
6.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 027-63-01263
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.