Yuma County, AZCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 9568 Turkey Hill Rd

Approved

Filed Feb 21, 2025 by Quinn Wexler, Keystone Backflow Testing · filed from phone

Report

Date of service
Feb 21, 2025
Assembly type
RP
Serial number
Z538303
Size
1
Test gauge serial
G-8151
Gauge calibration date
Nov 4, 2024
Check valve 1
5.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 027-93-01021
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

9568 Turkey Hill Rd
Owner: Blake Danner
Parcel 027-93-01021