Backflow assembly test · 8240 Fox Run Trl
ApprovedFiled Oct 31, 2025 by Jordan Pruitt, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Oct 31, 2025
- Assembly type
- RP
- Serial number
- Z240158
- Size
- 3/4
- Test gauge serial
- G-6852
- Gauge calibration date
- Jan 10, 2025
- Check valve 1
- 8.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.1 psid
- Relief valve opened at
- 2.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 027-40-01312
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.