Backflow assembly test · 1845 Pine Knoll Dr
ApprovedFiled Mar 9, 2026 by Sam Fairley, Northstar Plumbing & Backflow · filed from phone
Report
- Date of service
- Mar 9, 2026
- Assembly type
- DC
- Serial number
- A497032
- Size
- 3/4
- Test gauge serial
- G-9914
- Gauge calibration date
- Mar 25, 2025
- Check valve 1
- 4.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 007-64-01256
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.