Backflow assembly test · 6694 Mill Creek Rd
ApprovedFiled Mar 17, 2025 by Emerson Brandt, Clearwater Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Mar 17, 2025
- Assembly type
- RP
- Serial number
- A592317
- Size
- 3/4
- Test gauge serial
- G-8927
- Gauge calibration date
- Aug 4, 2024
- Check valve 1
- 6.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Relief valve opened at
- 2.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 007-31-01189
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
6694 Mill Creek Rd
Owner: Avery Kessler
Parcel 007-31-01189