Backflow assembly test · 6459 Turkey Hill Trl

Approved

Filed Jan 2, 2026 by Jamie Wexler, Northstar Plumbing & Backflow · filed from phone

Report

Date of service
Jan 2, 2026
Assembly type
RP
Serial number
A246838
Size
1
Test gauge serial
G-3809
Gauge calibration date
Sep 15, 2025
Check valve 1
0.5 psid
Check valve 1 closed tight
No
Check valve 2
2.5 psid
Relief valve opened at
2.9 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 007-17-01271
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6459 Turkey Hill Trl
Owner: Avery Ellery
Parcel 007-17-01271