← Backflow review queue
Backflow assembly test · Corner Market
ApprovedFiled Apr 20, 2026 by Parker Danner, Valley Backflow Testing · filed from phone
Report
- Date of service
- Apr 20, 2026
- Assembly type
- RP
- Serial number
- B828295
- Size
- 2
- Test gauge serial
- G-1615
- Gauge calibration date
- Nov 8, 2025
- Check valve 1
- 8.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 2.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 007-83-01007
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
9018 Turkey Hill Ct
Owner: Wexler Holdings LLC
Parcel 007-83-01007