Report
- Date of service
- Nov 17, 2026
- Assembly type
- PVB
- Serial number
- K457511
- Size
- 3/4
- Test gauge serial
- G-2310
- Gauge calibration date
- Apr 23, 2026
- Check valve 1
- 5.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 131-66-01184
- Readings in range, no flags
- Result: passing. Next due date resets when approved.