Backflow assembly test · Riverside Self Storage
ApprovedFiled Jan 7, 2025 by Hayden Okafor, Northstar Backflow Testing · filed from phone
Report
- Date of service
- Jan 7, 2025
- Assembly type
- DC
- Serial number
- B949871
- Size
- 1 1/2
- Test gauge serial
- G-6812
- Gauge calibration date
- Jun 30, 2024
- Check valve 1
- 7.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Okafor, current on the service date
- All required fields present
- Address matches parcel 131-92-01134
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
1959 Sycamore Trl
Owner: Harlow Holdings LLC
Parcel 131-92-01134