Sebastian County, ARCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Maple Leaf Medical Offices

Approved

Filed Apr 22, 2026 by Morgan Pruitt, Northstar Plumbing & Backflow · filed from phone

Report

Date of service
Apr 22, 2026
Assembly type
RP
Serial number
K505598
Size
2
Test gauge serial
G-7179
Gauge calibration date
Sep 12, 2025
Check valve 1
3.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
1.4 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 131-43-01061
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

3846 Quarry Dr
Owner: Danner Holdings LLC
Parcel 131-43-01061