← Backflow review queue
Backflow assembly test · 7579 Turkey Hill Ln
ApprovedFiled Jun 30, 2023 by Hayden Okafor, Northstar Backflow Testing · filed from phone
Report
- Date of service
- Jun 30, 2023
- Assembly type
- RP
- Serial number
- B598327
- Size
- 3/4
- Test gauge serial
- G-5034
- Gauge calibration date
- Sep 27, 2022
- Check valve 1
- 5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.3 psid
- Relief valve opened at
- 4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 131-90-01137
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
7579 Turkey Hill Ln
Owner: Avery Okafor
Parcel 131-90-01137