Sebastian County, ARReports, deadlines and notices in one place
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 8563 Sycamore Rd

Approved

Filed Jan 8, 2026 by Parker Ashby, Northstar Plumbing & Backflow · filed from phone

Report

Date of service
Jan 8, 2026
Assembly type
RP
Serial number
B665599
Size
3/4
Test gauge serial
G-2268
Gauge calibration date
Nov 2, 2025
Check valve 1
3.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
2.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Ashby, current on the service date
  • All required fields present
  • Address matches parcel 131-75-01192
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8563 Sycamore Rd
Owner: Riley Hollins
Parcel 131-75-01192