Sebastian County, ARCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 4519 Mill Creek Rd

Approved

Filed Dec 10, 2025 by Hayden Okafor, Northstar Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Dec 10, 2025
Assembly type
RP
Serial number
W641417
Size
3/4
Test gauge serial
G-6593
Gauge calibration date
Aug 4, 2024
Check valve 1
6.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
1.8 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 131-17-01202
  • RP relief valve must open at 2.0 psid or more.
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

4519 Mill Creek Rd
Owner: Reese Pruitt
Parcel 131-17-01202