Backflow assembly test · 443 Meadow Lark Dr
ApprovedFiled Oct 27, 2026 by Hayden Pruitt, Summit Backflow Testing · filed from phone
Report
- Date of service
- Oct 27, 2026
- Assembly type
- PVB
- Serial number
- A416959
- Size
- 3/4
- Test gauge serial
- G-3742
- Gauge calibration date
- May 7, 2026
- Check valve 1
- 4.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 131-14-01057
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.