Sebastian County, ARCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Blue Heron Animal Hospital

Approved

Filed Jul 3, 2024 by Hayden Pruitt, Summit Backflow Testing · filed from phone

Report

Date of service
Jul 3, 2024
Assembly type
RP
Serial number
B715997
Size
4
Test gauge serial
G-5919
Gauge calibration date
Jan 23, 2024
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 131-69-01172
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

6527 Orchard Dr
Owner: Danner Holdings LLC
Parcel 131-69-01172