Backflow assembly test · 9558 Stone Gate Dr
ApprovedFiled Nov 20, 2023 by Jamie Ashby, Summit Backflow Testing · filed from phone
Report
- Date of service
- Nov 20, 2023
- Assembly type
- DC
- Serial number
- B304765
- Size
- 1
- Test gauge serial
- G-5992
- Gauge calibration date
- Feb 7, 2023
- Check valve 1
- 8.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Jamie Ashby, current on the service date
- All required fields present
- Address matches parcel 143-93-01033
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.