Backflow assembly test · Corner Elementary School
ApprovedFiled Nov 13, 2024 by Blake Wexler, Lakeside Plumbing & Backflow · filed from phone
Report
- Date of service
- Nov 13, 2024
- Assembly type
- DC
- Serial number
- A543417
- Size
- 2
- Test gauge serial
- G-1953
- Gauge calibration date
- Feb 21, 2024
- Check valve 1
- 6.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Blake Wexler, current on the service date
- All required fields present
- Address matches parcel 143-56-01195
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
2196 Ridgeview Ln
Owner: Hollins Holdings LLC
Parcel 143-56-01195