← Backflow review queue
Backflow assembly test · 3405 Sycamore Way
ApprovedFiled Nov 15, 2025 by Casey Danner, Lakeside Plumbing & Backflow · filed from phone
Report
- Date of service
- Nov 15, 2025
- Assembly type
- PVB
- Serial number
- K235604
- Size
- 1
- Test gauge serial
- G-5614
- Gauge calibration date
- Apr 16, 2025
- Check valve 1
- 3.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Casey Danner, current on the service date
- All required fields present
- Address matches parcel 143-59-01308
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
3405 Sycamore Way
Owner: Hayden Ramirez
Parcel 143-59-01308