Backflow assembly test · 4815 Old Church Way
ApprovedFiled Aug 26, 2025 by Reese Fairley, Clearwater Backflow Testing · filed from phone
Report
- Date of service
- Aug 26, 2025
- Assembly type
- DC
- Serial number
- A651521
- Size
- 3/4
- Test gauge serial
- G-1188
- Gauge calibration date
- Mar 17, 2025
- Check valve 1
- 8.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 143-67-01032
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
4815 Old Church Way
Owner: Alex Nguyen
Parcel 143-67-01032